Optional Features
A)Construction options:
1. Metal mesh on condenser section.
2. Optional supply/return air configurations, optional bottom supply and return type.
3. Evaporator with treated anti-corrosion protection for coils (blue fins)for copper/aluminum coils only.
4. “25mm (1”)” or “50mm(2”)” thick flat filter.
5. Economizer option with fresh, return and exhaust air dampers with cowl.
If this option is installed in the unit the unit has the ability to work with free cooling or free heating mode allowing it to exploit
the external environmental condition as much as possible, since it avoids turning on the heaters and the compressors. This
function can be achieved by controlling the opening/closing of the external air damper. With reference to the difference
between the outdoor air temperature(std)/enthalpy and the indoor air temperature(std)/enthalpy.
6. High Static condenser fan option will also required a sealed + drain condensing section.
7. Upgraded Evaporator Fan Motor Drives.
B)Electrical options:
1. Power circuit breaker for each motor.
2. Main power molded case circuit breaker for the whole unit (can also be available with an external handle as an option).
3. Low ambient control:
The refrigeration systems in all unit are inherently designed to operate efficiently, without extra controls or modifications. To
permit the unit to operate in low ambient condition a head pressure control can be Installed either by:
ON/OFF condenser fans sequencing (for models with 2 condenser fans).
3 speed of the condenser fan motor.
4. Earth leakage relay for each compressor.
5. Earth leakage relay for the whole unit.
6. External overload relay for each motor.
6
7. Power factor correction capacitor.
8. Automatic or manual provision for pump down operation of each compressor stop.
9. Building automation system interface. Interfacing with other building management systems can be Achieved by an optional
card which can communicate with other devices using the serial communication port.
10. Voltage monitor controller (phase sequence relay) for monitoring the main incoming power supply for the unit which
provides protection from single-phasing, under-voltage, phase-voltage imbalance and phase-non-sequence
Refrigeration options:
1. Heat pump packaged unit with 4-way reversing valve, suction accumulator is a standard feature in heat pump option.
2. Pressure gauges for each refrigeration circuit (high/low pressure gauges).
3. Hot gas bypass (where low-local situation occurs and where it is necessary avoid low suction pressure and “compressor
cycling”)
4. Extra refrigerant accessories such as suction accumulators (for cooling units only), refrigerant liquid receivers, oil
separators etc..
5. Solenoid valve for heat pump mode.
6. High and low pressure controller for models